Hvac system design requires methodical assessment of the options – xylem applied water systems – united states bp gas prices chicago

##########

Rising energy costs and a movement toward sustainability are driving changes in the commercial HVAC market. gas finder rochester ny As design engineers, building owners and mechanical contractors focus on increasing comfort and maintaining air quality while reducing overall energy consumption, the technology and components of HVAC systems are constantly being re-evaluated.

With heating and cooling among the largest costs for most buildings, building owners are intent on finding new and effective approaches for new buildings and improving performance of existing facilities. And as the industry continues the shift to sustainable building practices that maximize building performance while minimizing environmental impact, the type of HVAC system is an important factor in realizing energy- efficiency targets. Additional factors such as safety and code compliance, and costs related to serviceability and life cycle are among those that also must be considered in evaluating HVAC systems.

While each has its place in commercial building HVAC systems, specifying engineers must be diligent in their review of project parameters and the applicable safety codes of ASHRAE Standards 15 and 34 to ensure they are making suitable selections. A closer examination of the key areas of differentiation between hydronic and VRF can also assist system designers in the process.

In contrast, system efficiency in VRF goes down based on the length of refrigerant pipe runs. ASHRAE Standards 15 and 34 define specific refrigerant concentration limits based on pounds of refrigerant per thousand cubic feet of interior volume beyond which acute toxicity is expected. gas near me cheap Typically, refrigerant charge in a VRF system is 4 to 6 pounds of refrigerant per ton of cooling. To adhere to ASHRAE 15 requirements, the VRF system may need to be broken down into smaller refrigerant circuits, thus compromising the benefits of diverting loads.

VRF systems are generally limited to buildings fewer than 10 stories because the length of piping runs must be limited and zoned properly in order to carry refrigerants and oil through the building in accordance with manufacturer guidelines. Long lengths of piping can jeopardize performance of the unit ranging from oil or refrigerant accumulation in the piping to de-rated efficiencies.

Care must be taken to ensure the refrigerant piping is not installed down hallways or in a large open office floor plan, both of which are considered means of egress per standards set by ASHRAE and the International Association of Plumbing and Mechanical Officials (IAPMO). gas jet compressor Even with ceiling-mounted fire suppression and sprinkler systems, these areas are still considered as the means of egress.

While it’s possible for leaks to develop in both hydronic and VRF systems, a leak in a VRF system can be deadly. VRF refrigerant leaks can’t be detected by either sight or smell, making them hard to find and repair. In spaces with minimal ventilation, large concentrations of refrigerant gas in the air can put people at risk of asphyxiation.

Hydronic systems with cooling units also require refrigerant to operate, but the average system uses 66 to 75 percent less refrigerant than a VRF system of the same size, according to the Hydronics Industry Alliance. Hydronic systems are not exempt from the ASHRAE and IAPMO codes that govern the HVAC and plumbing industries, however, the refrigerant in a hydronics system is typically contained within a mechanical room, which, by code, is required to have the proper ventilation to deal with a potential leak.

The same cannot be said for VRF refrigerants. gas prices going up 2016 The Environmental Protection Agency issued major changes to the Section 608 rules of the Clean Air Act, which govern the handling, use and sale of refrigerants. Most notable is the regulation banning the use of hydrofluorocarbons such as R-410A in new chillers (air-cooled, water-cooled, scroll, screw and centrifugal), rooftop units and VRF systems beginning in 2024.

Under the updated rules, the EPA expanded the refrigerant management program, extending the regulations to non-ozone-depleting substitutes such as hydrofluorocarbons. gas 78 industries This action lowers the allowable leak rate for comfort cooling and refrigeration appliances. It also incorporates industry best practices, such as verifying repairs and conducting annual leak inspections for systems that have lost a small amount of their refrigerant charge.

Proprietary VRF systems require specialized technicians for installation and maintenance — which can drive up costs — compared to hydronic water systems designed with universal components that can be installed and serviced by any HVAC service technician. Components in a hydronic system are factory made and tested, reducing rate of failure after installation.

The initial cost of a hydronic system is generally lower, and systems offer a much wider range of flexibility for components, operation and maintenance, both in terms of parts and service. r gas constant kj Advanced systems include application of technologies such as integrated and single-pipe systems that dramatically reduce piping and costs, and pumps equipped with variable speed drives that increase energy efficiency.

At lower temperatures, hydronic systems are more reliable than VRF systems. That’s because a VRF system may require a supplementary heat source in cold climates, such as electric heat, which could negate the energy efficiency of the system. Without another heat source, the VRF compressor can be set to run at maximum capacity for the morning warm-up, but that takes more electricity, potentially negating any efficiency benefits, including reduced energy costs.

VRF system can provide simultaneous heating and cooling, and can recover heat from one zone and use it in another. r gasquet tennis This is effective in buildings with multiple temperature zones, such as a hotel. However, a VRF system does not have the capability of storing energy. Water in a hydronic system can draw the heat or chill out of a room and carry that energy back to the system for storage and later use, reducing energy consumption and costs.

These and other considerations have relevancy for building owners, architects, design engineers and all those who have a stake in commercial building HVAC system design, installation, operation and maintenance. Those who influence system selections must be diligent in their analysis to ensure systems are code compliant, energy efficient and adaptable to future energy sources. The most efficient systems in terms of cost, performance and efficiency will be in demand to help meet energy goals and keep building costs in line.

– Commercial Buildings Services market for Xylem. He holds a bachelor of science degree in polymer and fiber engineering from Auburn University. He has nearly 10 years of experience in the HVAC industry in a variety of sales, training and marketing roles. In addition, he is an active HIA-C and ASHRAE chapter member and is LEED AP certified.